Standby Generator Sizing & Turnkey Budget Estimator

Estimate running and motor-starting load, pick the right generator tier on natural gas or propane, see whether load shedding lets you step down a size, and get an itemized 2026 installed cost.

NEC 702.4 Standby Generator Sizing & Budget Sheet

Optional standby system · Reilly Electrical

Coverage & fuel
Coverage strategy
Fuel

Air-cooled generators are rated on LP. On natural gas they deliver roughly 10% less: a 24 kW unit gives about 21 kW.

Home & HVAC
sq ft

Compressor starting current is usually what forces a bigger generator. A soft starter cuts the surge by roughly 60%.

Heavy 240 V loads on backup
Load management NEC 702.4

NEC 702.4 lets a standby generator be sized for less than the full calculated load when an automatic load management system keeps it from overloading. Modules switch large loads off in priority order and back on when capacity returns.

Site conditions

Prepared with the Reilly Electrical calculator on . Reproduce this calculation:

Preliminary planning estimate only. Final service sizing, code edition and installed price are determined by a licensed electrician after an on-site survey and by the local Authority Having Jurisdiction (AHJ) and serving utility. Reilly Electrical · reillyelectrical.com · estimates@reillyelectrical.com

How the generator is sized

A standby generator has to do two things: carry the running load for hours, and survive the few seconds when the biggest motor in the house starts. The calculator models both and picks the smallest standard tier that clears the stricter of the two.

  1. Running load. A base load for lighting, refrigeration, furnace blower and receptacles (scaled by square footage, smaller for an essential-circuits panel), plus the A/C running load (about 1.2 kW per ton) and the heavy 240 V loads you choose to back up, diversified at 75% when more than one is present.
  2. Motor starting. The running load with the largest motor at its starting surge instead of its running draw (about 5 kW per ton for an A/C compressor without a soft starter).
  3. Required rating. The larger of running ÷ 0.8 (keeps the unit under 80% continuous) and peak ÷ 1.25 (short-term surge capacity).
  4. Fuel. The requirement is compared with the natural gas output when you choose NG, and with the LP rating when you choose LP.
  5. Load shedding (NEC 702.4). With modules, managed heavy loads never run together: only the largest counts at full value.
Tier (LP rating)Natural gas outputCoolingUnit price, 2026
14 kW≈ 12 kWAir$4,000 – $4,800
18 kW≈ 17 kWAir$4,600 – $5,400
22 kW≈ 19.5 kWAir$5,200 – $6,200
24 kW≈ 21 kWAir$5,800 – $6,500
26 kW≈ 22.5 kWAir$6,200 – $7,200
30 kW≈ 27 kWLiquid$11,000 – $14,000
38 kW≈ 34 kWLiquid$13,000 – $17,000
48 kW≈ 45 kWLiquid$16,000 – $21,000

Outputs vary by manufacturer and model; your dealer will confirm against the exact unit's spec sheet and your gas meter's capacity. See the standby generator guide for brand trade-offs and the methodology page for the full model.