NEC 2026 Load Calculation Changes: Article 120 vs. Article 220

The 2026 code renumbered every residential load calculation section and lowered the service lighting load to 2 VA per square foot. Here is the section map, a worked comparison, and how to tell which edition your city enforces.

Electrician measuring a panel with a digital multimeter
220.82 → 120.82Same method, new number

Article 220 became Article 120

The 2026 edition of the National Electrical Code (NFPA 70) moved the calculation rules for branch circuits, feeders and services out of Chapter 2 and into Chapter 1 as Article 120. The math is largely the same; the section numbers are not. If your electrician, inspector or utility quotes "220.82" and your plan reviewer asks for "120.82", they are talking about the same optional method.

Section mapping for the rules most residential service calculations use. Confirm against the edition your AHJ has adopted.
What it coversNEC 2023NEC 2026
Optional method — single dwelling220.82120.82
Optional method — existing dwelling (adding load)220.83120.83
Optional method — multifamily220.84120.84
Existing loads from demand history / load study220.87120.87
Dwelling general lighting load (service / feeder)220.41 · 3 VA/sq ft120.41 · 2 VA/sq ft
Branch-circuit count & panel spaces3 VA/sq ft120.13 · 3 VA/sq ft retained
EV charging equipment load220.57120.57
Surge protection on dwelling services230.67230.67 (unchanged)
Outdoor emergency disconnect230.85230.85 (unchanged)

The 2 VA per square foot change

For decades, dwelling general lighting and receptacle load was calculated at 3 VA per square foot. Measured demand in modern homes — LED lighting, efficient electronics — runs far below that. NEC 2026 120.41 lowers the figure to 2 VA per square foot for sizing feeders and services, while 120.13 keeps 3 VA per square foot for working out how many general-purpose branch circuits (and panel spaces) a home needs.

2,400 sq ft home, optional methodNEC 2023NEC 2026
General lighting7,200 VA4,800 VA
Small appliance (2) + laundry (1)4,500 VA4,500 VA
Range 12,000 · dryer 5,000 · water heater 4,500 · dishwasher 1,200 · disposal 90023,600 VA23,600 VA
General load G35,300 VA32,900 VA
10,000 VA @ 100% + remainder @ 40%20,120 VA19,160 VA
A/C 5,000 VA (gas heat)5,000 VA5,000 VA
48 A EV charger11,520 VA11,520 VA
Total demand36,640 VA = 152.7 A35,680 VA = 148.7 A

The saving is real but modest: 40% of 1 VA per square foot, about 4 A on a 2,400 sq ft home. It rarely turns a failing calculation into a passing one on its own, but on a borderline 150 A service it can be the margin that avoids an upgrade.

Electrician measuring a panel with a digital multimeter
A calculation is a planning tool. Before anything is installed, an electrician confirms the panel and service on site.

Two service requirements that add cost

NEC 230.67 — surge protection

Since the 2020 edition, every service supplying a dwelling unit must have a listed Type 1 or Type 2 surge protective device when the service is installed or replaced. It is integral to the service equipment or mounted next to it. Budget $150–$450 installed.

NEC 230.85 — outdoor emergency disconnect

One- and two-family dwellings need a readily accessible emergency disconnect outside the building, so first responders can shut off power without entering. Meter-main combinations satisfy it neatly; retrofits on existing panels cost $300–$900. It applies when a service is installed, upgraded or replaced.

Which edition applies to you

The NEC is a model code. Each state — sometimes each city or county — adopts an edition on its own schedule, often with local amendments. In 2026 many jurisdictions still enforce NEC 2020 or NEC 2023 while early adopters move to NEC 2026. Check before you rely on the 2 VA figure:

  1. Search your state electrical board or building codes council for the adopted NEC edition and effective date.
  2. Ask your city or county building department whether it has local amendments.
  3. Ask the electrician which edition they will cite on the permit load calculation.

The load calculator lets you switch between NEC 2023 and NEC 2026 so you can see both results.

Run the calculation under both editions

Toggle NEC 2023 and NEC 2026 in the calculator and print the sheet for the edition your AHJ enforces.